Agilent Technologies DP111 Dokumentacja Strona 220

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 452
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 219
DriveBus Interface - CI858 Section 5 Maintenance
220 3BSE036351-510 A
Dbus;Tx1 LED is OFF The unit is not properly configured or unit error.
Check the CB for a failure message.
If there is no failure message replace the
CI858 unit.
I/O;Rx1 LED is ON (not
flashing)
The unit is not receiving data.
Check all cables and connections.
If there is no failure message replace the
CI858 unit.
I/O;Rx1 LED is OFF No signals are sent to the unit or unit error.
Check all cables and connections.
Replace the CI858 unit.
I/O;Tx1 LED is ON (not
flashing)
The unit is not transmitting data.
Check the CB for a failure message.
If there is no failure message in the CB
replace the CI858 unit.
I/O;Tx1 LED is OFF The unit is not properly configured or unit error.
Check the CB for a failure message.
If there is no failure message replace the
CI858 unit.
CI858 supports hot swap.
Table 38. DriveBus CI858 – Fault-Finding (Continued)
Fault Possible Cause and Corrective Action
Przeglądanie stron 219
1 2 ... 215 216 217 218 219 220 221 222 223 224 225 ... 451 452

Komentarze do niniejszej Instrukcji

Brak uwag